Protection
Protective Item
|
Trip Time
|
Description
|
Over-current
|
O-TIME
|
Is
|
Phase Loss
|
3 sec
|
-
|
Locked Rotor
|
0.5sec after elapse of dt
|
2times OC setting value
|
Specification
Current Setting Range
|
Current
|
05
|
0.5 ~ 6A
|
30
|
3.0 ~ 30A
|
60
|
10 ~ 60A
|
Starting delay time
|
D-TIME
|
OFF
|
Trip time
|
O-TIME
|
0.5, 1~10 sec
|
Operating t-c characteristic
|
Over-Current
|
Definite
|
Tolerance
|
Current
|
±5%
|
TIME
|
±5%
|
Environment
|
Temperature
|
Operation
|
-20 ~60℃
|
Store
|
-30 ~80℃
|
Humidity
|
30~85% RH Non-condensing
|
Control Power
|
220 : 220VAC±15%, 50/60Hz
|
110 : 110VAC ±15%, 50/60Hz
|
Output relay
|
2-SPST
|
3A / 250VAC Resistive
|
Insulation
|
Between casing and circuit
|
Over 10MΩ, 500VDC
|
Dielectric Strength
|
Between casing and circuit
|
2000VAC 60Hz, 1min
|
Between open contacts
|
1000VAC 60Hz, 1min
|
between circuit
|
2000VAC 60Hz, 1min
|
Reset
|
Manual/Electrical
|
Installation
|
35mm DIN-Rail or Panel Mounting
|
EOCR-SSD05 EOCR-SSD30
|